| Output Power |
3750W (dual feed) / 3000W (single feed) |
| Output Voltage |
51V and 12V_SB outputs are electrically isolated. |
| Line regulation |
+/-1% |
| Load regulation |
load line, output voltage vs. output current with 2V droop. |
| Ripple & Noise |
< 520mV pk-pk@V1, <200mV pk-pk@V2 |
| Rise time |
< 500 ms |
| Turn On Delay |
< 3 sec |
| Dynamic response |
Output shall stay within the regulation from 54VDC to 50VDC for current step change of 50% -100% of full load. |
| Over current protection |
115-125% of Full load |
| Short circuit protection |
Shall provide hiccup type of protection with 5 re-tries and shutdown the main output. |
| Over voltage protection |
Latching Type |
| Current share |
Current sharing via active and passive method for main output. |
| EEPROM & I2C bus |
PS with a serial EEPROM communicates information to the system processor through I2C bus |
| Microcontroller |
PSU remote shut off, LED status monitored and controlled through microcontroller. |
| Thermal protection |
PWM Converter disabled when the internal temperature exceeds safe operating range |
| Under voltage |
Capable to withstand any input under voltage for unlimited time without damage. |
| Fan fail |
Power Fail signal also indicate warning of an internal fan failure |
| Hot swapping |
Hot swappable |